PadPuls M2
The 2-channel pulse adaptor PadPuls M2 allows the use of up to 2 meters with pulse output as M -Bus slaves.

-
Two separated pulse inputs
-
Safe detection of up to 15 pulses per second at each input
-
Pulse debouncing
-
Pulse value free adjustable
-
Plug-in terminals simplify the installation wiring
-
Unit free selectable (e.g. Wh, kWh, MWh, kJ, m3, l,...)
-
Counter length: 8 decimal digits
-
Due-date function with integrated realtime clock
-
One yearly value and 15 monthly values (optional)
-
M-Bus protocol according to EN13757-2 and -3
-
Fully parameterizable by M-Bus, including overwrite protection
-
Transmission rate: 300 and 2400 baud with auto baud detection
-
Fully operable in case of M-Bus failure by integrated battery
-
Case for wall mounting W x H x D: 80 x 80 x 52 mm
-
Two battery options available
-
Protective class IP 54 (IP65 is possible)
The devices of the PadPuls M2 series adapt up to two conventional meters with pulse output to a M-Bus system. The two counter inputs are nearly free parameterizable and fit in already existing installations.
Optionally the user can activate a tariff function, by which energy or volume pulses can be accumulated in separate meter readings for primary and secondary tariffs. O one pulse signal and one changeover signal for the tariff are required, for example out of a ripple control receiver from the electricity supplier.
The integrated battery ensures that the impulse adaptor is fully operable, even if the M-Bus network fails. Additional security is provided by the periodic saving of the meter readings in nonvolatile memory.

Technical Data
Power supply
Remote supply by M-Bus with automatic switch to battery on bus fail
Bus operation
max. 1.5mA (1 unit load), no load of battery
Battery lifetime 0,23Ah
10 years at max. 80 failure days p.a. (changeable coin type battery)
Batterie lifetime 1,80Ah
10 years at max. 250 failure days p.a.
Operating temperature
0..55 °C
Battery expectancy
Current draw typ. 8μA
Pulse inputs
2, individually programmable
Potential-free contact
Contact voltage
2,5V .. 3,6V
Contact current
30μA
Cable pulse generator
max. 10m
Debouncing time
5ms
Potential
free of potential
Resistance
open > 1MΩ, closed < 2kΩ
Contact duration
min. 30ms
Temperature range
Pulse frequency
max. 14 Hz
Tariff signal
potential free (data see above)
Floating contact
S0 according to DIN43864
M-Bus protocol
according to EN13757-2 and -3
Baudrates
300, 2400 and 9600 baud (automatic detection)
Mounting
Wall mounting
Protective class
IP54 (IP65 possible)
Dimensions
WxHxD:80x80x52mm
Transmission rate
Addressing
Card IM001
Housing IM001G
Housing IM001GC
Housing IM002GC
Order Information
Order Number
Description
IM003G
PadPuls M2
Both versions including configuration software MBCONF